EL7411 OPT and CSTCA

EL7411_OPT adds CSV, CSP, CST and CSTCA choices through the shared Ex72xx OPT dispatcher, with an EL7411-specific PDO and timing policy. The existing EL7411 and EL7411_CSP descriptors, substitutions and panels are unchanged.

Examples and defaults

# Same four PDOs as the legacy EL7411 CSV configuration.
${SCRIPTEXEC} ${ecmccfg_DIR}addSlave.cmd "HW_DESC=EL7411_OPT"

# Torque with externally commanded electrical commutation angle.
${SCRIPTEXEC} ${ecmccfg_DIR}addSlave.cmd "HW_DESC=EL7411_OPT,OPT='MODE=CSTCA,DIAG=1,INFO2=INPUTS'"

# Position control with optional touch-probe status and temperature.
${SCRIPTEXEC} ${ecmccfg_DIR}addSlave.cmd "HW_DESC=EL7411_OPT,OPT='MODE=CSP,TP=1,DIAG=1,INFO2=TEMP'"

Configure the motor and feedback after loading the slave, using the appropriate EL7411 motor/encoder configuration for the installed hardware. The wrapper sets ECMC_EC_COMP_TYPE=EL7411; it does not replace motor or feedback commissioning.

OptionDefaultChoices
MODECSVCSV, CSP, CST, CSTCA
TP00 or 1; optional touch-probe status only
DIAG00 or 1; actual velocity, torque and DC voltage
INFO2NONENONE, INPUTS, TEMP
ENC_STAT00 only; EL7411 has no documented EL72xx encoder-status PDO

Channel 1 overrides (MODE_1, TP_1, DIAG_1, INFO2_1, ENC_STAT_1) follow the shared option precedence. Second-channel options are rejected. Invalid combinations fail before slave reset or hardware configuration. INFO2=ERRORS is not offered for EL7411; use the HW diagnostic-buffer button.

The default process image contains drive control, velocity demand, primary position and drive status only. Default CSP similarly matches the existing EL7411_CSP PDO set. With MODE=CSP,DIAG=1, following error is additionally mapped at 0x6010:06. Torque offset is not mapped on EL7411.

INFO2=INPUTS uses a separate EL7411 record template: its hardware-enable/STO input level is bit 12, whereas the EL72xx template uses bit 8. The shared inputs panel displays that level through Drv01-STO01; this is a diagnostic input level, not a complete safety-state assessment. The Info2 selector SDO 0x8010:3A is a UINT8 and is written as a one-byte value.

CSTCA target and readbacks

CSTCA uses target torque plus an externally commanded electrical angle. The startup SDO 0x7010:03 is set to 11. CSV, CSP and CST use 9, 8 and 10.

Logical EtherCAT entryPDOObjectType
torqueSetpoint010x16020x7010:09S16
commutationAngle010x16030x7010:0EU16

The following PV suffixes use the normal slave prefix $(IOC):m$(MasterID)s$(SlaveID)-:

Writable targetDemand readbackUnits
Drv01-TrqDrv01-Trq-RBPercent, 0.1 per raw count
Drv01-ComAngleDrv01-ComAngle-RBElectrical degrees, 360/65536 per raw count

The angle target is bounded to 0…359.9945068359375 degrees, corresponding to raw U16 values 0…65535. The angle readback reports the commanded PDO value; it is not a measured rotor angle. CSTCA controls the electrical angle directly, so it can produce motor movement when enabled.

Panels

The wrapper uses the existing 128 × 500 OPT overview, including its HW EtherCAT diagnostic-buffer shortcut. CfgMode=3 identifies CSTCA; CSV/CSP/CST retain values 0/1/2. The channel panel shows a CSTCA details link only when that mode is configured. The EL/EP/ELM72xx wrappers also support CSTCA, with a different input PDO policy.

ecmcEX72XX_OPT_cstca.ui provides torque controls and a writable angle, angle demand readback and > trend button in a compact 350 × 332 panel. Press Enter to write torque or angle. With DIAG=1, actual torque is also shown. With DIAG=0, it displays Not mapped and does not subscribe to an absent actual-torque PV. DS402 enable/disable and the state guide remain available without an axis object. Coordinate direct target writes with the axis configuration whenever an axis controls the drive.

CSV/CSP/CST, diagnostics, touch-probe and temperature panels are shared with Ex72xx OPT. Velocity and position demand records default to the legacy raw scale (1, RAW). VEL_ESLO, VEL_EGU, POS_ESLO and POS_EGU can override demand/velocity record scaling; they do not change the drive’s SDO scaling. Primary encoder position retains the existing raw-position record convention.

Timing and validation

The default DC schedule and current initialization match the legacy EL7411: Sync 0 is 62500 ns, Sync 1 is the application period minus 62500 ns, both 0x1C32 and 0x1C33 receive sync-mode 3 and the application period, and the initial peak-current SDO is 1000 mA. Motor configuration can overwrite that current setting. SYNC_0_CYCLE, SYNC_0_SHIFT, SYNC_1_CYCLE, SYNC_1_SHIFT, WATCHDOG_DIVIDER and WATCHDOG_INTERVALS use the shared override conventions. No EtherCAT port-wiring check is enabled. The shared startup-delay policy is retained.

Static integration checks compare default CSV/CSP mappings to the legacy configurations, exercise all mode/feature combinations, expand databases, verify angle scaling and limits, follow visible panel links and compile the Qt panels. They do not connect to a drive; commissioning on target hardware remains necessary.

Mapping sources: Beckhoff EL7411 standard objects, configuration data, and commissioning with status word and control word.