The N6 optional configuration combines fine open-loop axis feedback with a periodic digital output generated inside the drive. Optional homing PDOs prepare the interface for referencing the output’s position source using homing method 35.
The working bench setup was an N6-1-1-1-S, firmware
FIR-v2542-B1080909, with a 200-full-step motor in cyclic synchronous
velocity mode (CSV). Fine counter feedback and an output every 100 full
steps were demonstrated together. Subsequent method-35 testing returned
scaled position to zero and produced a repeatable first-edge shift,
documented below. Full homing/error handling still needs commissioning. Homing is commanded through the normal axis interface
and does not execute automatically at IOC startup.
Build/install both updated modules: ecmccfg supplies the hardware, records
and panels; ecmccomp supplies Drive-Generic-PositionOutput.
${SCRIPTEXEC} ${ecmccfg_DIR}addSlave.cmd "HW_DESC=N6-1-1-1-S_OPT,OPT='RAW_POS=1,HOMING=1'"
${SCRIPTEXEC} ${ecmccfg_DIR}applyComponent.cmd "COMP=Motor-Generic-2Phase-Stepper,CH_ID=1,MACROS='I_MAX_MA=400,I_STDBY_MA=100,STEPS=200,INV_DIR=0'"
${SCRIPTEXEC} ${ecmccfg_DIR}applyComponent.cmd "COMP=Drive-Generic-PositionOutput,CH_ID=1,MACROS='FULL_STEPS=100,OUTPUT=1,ARM=1,N6_IO_24V=0'"
Apply the motor first, then the position-output component, before applying
EtherCAT configuration. The output component checks the raw mapping, motor
configuration and supported interval. Motor INV_DIR=0 is required. Applying
the motor again after the output component is rejected because it would
restore position units and change the output period.
The complete example is
examples/PSI/lab_setup/N6/startup_position_output_100_steps.cmd, with
cfg/axis_position_output.yaml for the axis. The ordinary startup.cmd
remains available for the base configuration. Restart the IOC after changing
PDO options. The former N6-1-1-1-S_POS_OUT hardware wrapper has been removed;
use _OPT instead.
| Option | Default | Effect when set to 1 |
|---|---|---|
RAW_POS | 0 | Map fine 6063:00 as positionActual01; name existing 6064:00 entry positionActualScaled01 |
HOMING | 0 | Add method, offset, drive homing speeds/acceleration and the sequence-26 trigger alias |
CAPTURE | 0 | Map 3241:01–0C capture control readbacks, counts and latched positions |
ANALOG_IN | 0 | Map both signed 3320:01–02 analog input values |
All options are independent and accept only 0 or 1. With all disabled,
the PDO mapping matches the base N6-1-1-1-S configuration. The motor
component type remains N6.
RAW_POS=1 appends the S32 6063 entry to existing TxPDO 1A03, increasing
that PDO from 16 to 20 bytes. The four TxPDO assignment slots are retained.
HOMING=1 appends 17 bytes to existing RxPDO 1603, increasing it from
4 to 21 bytes without adding an RxPDO assignment slot. These options map
entries; they do not change position units, route outputs or execute homing.
The trigger alias is process-image data over existing controlword bit 4;
it adds no EtherCAT PDO bytes.
The runnable all-options example is
examples/PSI/lab_setup/N6/startup_opt_all.cmd. It reuses the 100-step
startup and M1 axis with N6_CAPTURE=1,N6_ANALOG_IN=1.
To enable all optional mappings directly:
HW_DESC=N6-1-1-1-S_OPT,OPT='RAW_POS=1,HOMING=1,CAPTURE=1,ANALOG_IN=1'
CAPTURE=1 exposes all twelve 3241 payload subindices as U32 readbacks:
| Group | Source | Subindices | PDO | Entry suffix |
|---|---|---|---|---|
| 01 | Home-switch capture | 01–04 | 1A00 | 01 |
| 02 | Input 3 capture | 05–08 | 1A01 | 02 |
| 03 | Input 4 capture | 09–0C | 1A02 | 03 |
Each group has captureControlNN, captureCountNN, capturePositionNN
and captureRawPositionNN. Corresponding PVs are CaptureNN-Control-RB,
CaptureNN-Count, CaptureNN-PosAct and CaptureNN-PosRaw. Position is in
configured drive position units; raw position is in sensor increments.
The EPICS records preserve the entire unsigned 32-bit range. For negative
positions, interpret the appropriate 32-bit two’s-complement value in the
application rather than treating the unsigned display as a distance.
The object dictionary marks these subindices TxPDO-only, including the
control fields. Mapping them does not arm capture or change input routing.
Configure the desired edge by SDO: 3241:01 for the home-switch source,
:05 for input 3, :09 for input 4. Values are 0 disabled, 1 rising,
2 falling and 3 both edges. Re-arming can reset the capture count.
For example, enable both-edge capture of input 3 on master 1/slave 0:
ethercat download -m1 -p0 --type uint32 0x3241 0x05 3
Check capture/input-routing behavior with the actual wiring and firmware;
in particular, its raw sensor value needs verification with our generated
open-loop counter. No automatic capture SDO writes are added by _OPT.
ANALOG_IN=1 maps analogInput01 and analogInput02 (S32, 3320:01–02)
in 1A03, with PVs AI01 and AI02. Values use the drive’s existing input
scaling and offsets. The records label them user, not volts; no voltage
conversion or analog-input configuration is applied by this option.
The groups are deliberately spread across existing PDOs because each PDO
has at most eight mapping entries. With all options enabled, TxPDO entry
counts are 1A00:6, 1A01:5, 1A02:5, 1A03:8; the four assignment slots
are retained. 1A03 is 28 bytes with raw position and both analog inputs.
| Configuration | positionActual01 | positionActualScaled01 |
|---|---|---|
Base descriptor or RAW_POS=0 | 6064, position in configured units | Not mapped |
_OPT, RAW_POS=1 | 6063, fine open-loop counter | 6064, position in configured units |
For the tested 200-full-step motor, the fine counter has nominally 3,276,800 counts/revolution, or 16,384 counts/full step. The example uses full-step engineering units:
epics:
unit: steps
drive:
numerator: 200
denominator: 3276800
encoder:
unit: steps
numerator: 200
denominator: 3276800
bits: 32
position: ec0.s$(ENC_SID).positionActual01
These are excerpts from the full YAML; use the complete example when
configuring an IOC and keep EtherCAT paths consistent with its axis
configuration. For degrees, use numerator 360 for both drive and encoder
and set both unit labels to deg. Check the corresponding scaling when
using another motor step count. Velocity remains in native increments per
second, so the drive and encoder scales remain matched.
The position-output component makes 6064 deliberately coarse: with
FULL_STEPS=100, one count is 100 full steps, or half a revolution on this
motor. Use 6063 for fine axis feedback. Both entries are available
simultaneously, but only one is the fine counter after changing 60A8.
The counter represents generated open-loop motion; it does not measure
rotor position or detect lost steps. Additional 60E4 position values also
use the configured position units; check external feedback channels if used.
Its 32-bit rollover and the output’s
behavior across rollover require application checks.
The output is generated inside the drive from scaled position 6064 and
its digital-output divider. It requires no cyclic PLC pulse generation or
NanoJ program. This configuration provides periodic position-related
triggering; it does not program arbitrary absolute compare positions or a
pulse width.
| Component macro | Default | Meaning |
|---|---|---|
FULL_STEPS | 100 | Full motor steps per output pulse |
OUTPUT | 1 | Physical digital output 1, 2 or 3 |
ARM | 0 | Initial output gate: 0 disabled, 1 enabled |
N6_IO_24V | 0 for the first output | 0 = 5 V; 1 = nominal 24 V/+UB_Logic |
N6_INPUT_PULLUP | Inherit motor; normally 0 | Shared input bias: 0 pull-down, 1 pull-up |
Supported intervals are 10^n * d, where n=0..6 and d is one of
1,2,4,8,16,32,64. Other intervals, such as 50 or 125 full steps, are
rejected. The component selects a canonical full-step unit 10^n and a
power-of-two divider.
All outputs on one drive share 60A8. For example, 100 and 200 steps use
the same unit of 100 with dividers 1 and 2, so they can coexist. Intervals
100 and 10 select different unit exponents and are rejected together.
Electrical settings are shared too: later output components inherit the
first output’s voltage and reject conflicting explicit voltage/bias choices.
Intervals are startup settings, not live scan parameters. Nothing is saved
to drive flash by this component.
For output 1 every 100 full steps, the important settings are:
| Object | Value | Purpose |
|---|---|---|
60E6:01 | 0 | Keep sensorless interface disabled |
60A8:00 | 0x02AC0000 | Position unit = 100 full steps |
3252:02 | 0x0910 | Route position divider 1 to output 1, gated by bit 16 |
323A:01 | 0 by default | Select 5 V I/O |
60FE:01, bit 16 | ARM | Output 1 gate |
With 200 full steps/revolution, subsequent edges were observed 180 degrees
apart: two output transitions per revolution. The expected steady time
between edges is 100 / abs(velocity in full steps/second) seconds
(or 180 / abs(velocity in degrees/second) when using degrees). An edge
is not a complete pulse: alternating rising/falling edges 100 steps apart
give a 200-step full cycle. See the observed first-edge shift after homing
below; verify waveform, pulse width, stop/restart and reversal on the bench.
The direct position-routing limit is 500 Hz.
Output 1 is on X4 pin 5, with GNDD on X4 pin 8.
The position-output component defaults to 5 V output levels. Select
N6_IO_24V=1 for nominal 24 V/+UB_Logic instead.
323A:01 selects both the output level and the digital input thresholds.
Selecting 5 V outputs therefore also selects 5 V input thresholds. It does
not configure the motor power supply; a motor supply such as 48 V is a
separate matter. The base hardware and motor component retain their
existing 24 V I/O default; the position-output component applies its own
selection afterwards. 323A:02 selects the shared input pull-up/pull-down.
The runtime gate controls are:
| PV suffix | Output-word bit | Function |
|---|---|---|
PosOut01-Ena | 16 | Output 1 gate |
PosOut02-Ena | 17 | Output 2 gate |
PosOut03-Ena | 18 | Output 3 gate |
Each has a corresponding -RB readback. For example, substituting the
actual slave prefix:
caput <prefix>PosOut01-Ena 0
caput <prefix>PosOut01-Ena 1
caget <prefix>PosOut01-Ena-RB
These controls gate the configured position-derived signal. Enabling a gate
does not command a single pulse or establish the pulse origin. Gate writes
preserve other output bits, including the brake bit 0. The component uses
bit-addressed WriteEcEntryEcPath; the records use asyn masks. Writing the
complete BO01-Arr word replaces all bits and can change other gates.
The hardware snippet loads all six gate control/readback records directly,
even when default substitutions are disabled. Output records use
PINI=0/NO so initialization preserves the configured gates.
examples/PSI/lab_setup/N6/startup_software_pwm.cmd is an isolated bench
candidate for fixed-frequency software PWM. It uses _OPT for masked output
gates, loads no motion axis, and keeps the drive disabled with zero velocity.
The test selects 5 V I/O and leaves the output gate disabled until explicitly
armed. The companion README_software_pwm.md contains the scope procedure.
The reusable SDO configuration is now in ecmccomp. The startup applies:
${SCRIPTEXEC} ${ecmccfg_DIR}applyComponent.cmd "COMP=Drive-Generic-PWMOutput,CH_ID=1,MACROS='FREQUENCY_HZ=2000,DUTY_PERCENT=50,OUTPUT=1,PWM_ID=0,ARM=0,N6_IO_24V=0'"
| Component macro | Default | Meaning |
|---|---|---|
FREQUENCY_HZ | 2000 | Plain integer 50..2000 Hz |
DUTY_PERCENT | 50 | Plain integer 0..100 percent; 0/100 give constant endpoints |
OUTPUT | 1 | Physical output 1..3 |
PWM_ID | 0 | Generator 0 (3260, source 0x12) or 1 (3261, source 0x13) |
ARM | 0 | Initial selected-output gate |
N6_IO_24V | 0 for first output; then inherit | Shared voltage selection |
N6_INPUT_PULLUP | Inherit motor | Shared input bias |
Apply it after the motor and N6_OPT. Outputs sharing a PWM_ID must use the same frequency/duty. PositionOutput and PWMOutput may use different physical outputs on one drive, but cannot claim the same output or disagree on shared I/O settings. The motor cannot be reapplied after either output component. Generator 0 / output 1 / 2 kHz / 50% is the bench-reported case; other choices still require commissioning. No extra frequency/duty PVs are added.
The EtherCAT manual distinguishes a 2 kHz software-PWM limit from the 500 Hz limit for other output sources. PWM is a fixed-frequency signal, not a faster position-divider mode. A successful PWM measurement does not prove that the 100-full-step position output can exceed its documented limit. A PWM carrier gated by position is also not automatically phase-aligned to position or guaranteed to produce one pulse per compare point.
The candidate uses 3260:01=2000 Hz, 3260:02=50 percent and
3252:02=0x1210 (PWM 0 to output 1, gated by bit 16). Source 0x12 is
explicitly listed in the newer
N6 Modbus TCP manual v1.2.1 for FIR-v2542,
section 7.1.2.3. The older EtherCAT v1.1.0 table omits that source despite
listing the PWM parameter objects. The user subsequently reported the PWM test working on the EtherCAT drive
on 2026-10-28. Numerical frequency/duty/jitter measurements were not supplied;
this is evidence for that tested setup, not other variants.
Run the dedicated startup instead of the position-output startup, connect
the scope to X4 pin 5 / GNDD pin 8, then arm PosOut01-Ena. Expected at
2 kHz/50%: a 500 microsecond full period with 250 microseconds high and low.
Disarm after measurement. The test also accepts 500, 1000 and 1500 Hz by
changing FREQUENCY_HZ in its component call and restarting. These are
checkpoints, not the only supported integer frequencies. No extra PDOs, motor
motion or drive-flash writes are needed. Restart the original 100-step
startup to restore position routing. The output was reported working; exact
frequency, duty and jitter still need recorded scope measurements.
No counter-clock input is documented for 3260; it provides frequency and
duty parameters. Output routing selects PWM or position, and its gate is a
60FE:01 bit. A PLC may gate PWM over a position window, but this gives
bursts of a time-based carrier rather than one edge per motor-step interval.
It does not bypass the documented 500 Hz position-divider limit.
Method 35 references the drive’s current position without a homing move.
With home offset 0 it can establish the zero of logical position 6064,
the source used for the periodic output. The manual explicitly states that
raw 6063 is not zeroed by drive homing. Referencing the ecmc axis using an
offset also leaves the drive counter unchanged and does not itself
reference the drive-side output source.
The observed first-edge shift after method 35 is described below. Drive referencing and ecmc axis-coordinate referencing remain separate operations, coordinated by sequence 26 in the example.
With HOMING=1, the process image initializes homingMethod01=35 and
homeOffset01=0. It also maps the drive homing dynamics, initialized to the
manual’s presets: switch-search speed 50, zero-search speed 10 and
acceleration 500. These are drive-defined user-unit values, separate from
the YAML homing parameters used by ecmc. Method 35 makes no search move;
configure and verify these values before using other drive homing methods.
Mode remains CSV (9) until a sequence changes it.
| Entry | Object/type | Purpose |
|---|---|---|
homingMethod01 | 6098:00, S8 | Homing method; optional PDO |
homeOffset01 | 607C:00, S32 | Offset in configured 6064 units; optional PDO |
homingVelocitySwitch01 | 6099:01, U32 | Switch-search speed; initialized to 50 |
homingVelocityZero01 | 6099:02, U32 | Zero/index-search speed; initialized to 10 |
homingAcceleration01 | 609A:00, U32 | Drive homing acceleration; initialized to 500 |
modeControl01 | 6060:00, S8 | Mode command: 6 homing, 9 CSV; already mapped |
modeActual01 | 6061:00, S8 | Mode acknowledgment; already mapped |
driveControl01 | 6040:00, U16 | Axis-owned controlword; already mapped |
driveCmdExe01 | B1 alias of 6040 bit 4 | Sequence-26 trigger; present with HOMING=1 |
driveStatus01 | 6041:00, U16 | Homing completion/error and drive status; already mapped |
With the 100-full-step position unit, a home offset of 1 means 100 full steps (180 degrees on the tested motor), not one native encoder increment. Use offset 0 when referencing the current scaled position to zero.
Additional PVs are Drv01-HomeMethod, Drv01-HomeOffset and
Drv01-ModeCmd, each with -RB, plus Drv01-ModeAct. Their command
readbacks report the process-image command values; Drv01-ModeAct is the
drive’s actual mode acknowledgment. Command records use PINI=0 so IOC
initialization does not overwrite the initialized method, offset or mode.
Additional command/readback pairs are Drv01-HomeVelTo, Drv01-HomeVelFrm
and Drv01-HomeAcc, also with PINI=0. Edit them while the axis is idle.
The EPICS edits use the nonnegative asynInt32 range; the mapped PDO type is U32.
The dedicated axis YAML now uses the existing drive-triggered homing sequence
26 (ECMC_SEQ_HOME_TRIGG_EXTERN), also used for SmarAct MCS2. No separate
PLC or C++ homing state machine is required for the example.
axis:
mode: CSV
autoMode:
modeSet: ec0.s$(DRV_SID).modeControl01
modeAct: ec0.s$(DRV_SID).modeActual01
modeCmdMotion: 9
modeCmdHome: 6
encoder:
homing:
type: 26
position: 0
trigg: ec0.s$(DRV_SID).driveCmdExe01.0
ready: ec0.s$(DRV_SID).driveStatus01.12
refAtHome: 1
timeout: 10
velocity:
to: 18
from: 18
acceleration: 36
deceleration: 36
postMoveEnable: true
postMovePosition: 0
This is an excerpt; retain the fine counter mapping and other axis settings from the complete example. The nonzero homing velocities/accelerations satisfy generic axis validation; drive method 35 makes no search move.
Sequence 26 switches to mode 6 and waits for the mode acknowledgment, asserts
the trigger, waits for a rising edge on statusword bit 12, clears the trigger
and references the ecmc encoder to position (zero here). The raw drive
counter and Enc01-PosAct remain unchanged; the axis position gains its
engineering offset. Normal axis enabling applies, so the motor may energize
even though bare drive method 35 itself does not require Operation enabled.
The existing sequence restores mode 9 through its post-home stage. Therefore
postMoveEnable is deliberately true, with postMovePosition equal to the
home position. This waits for CSV mode acknowledgment and skips the move
because the referenced position already equals the target. If these two
positions are changed, keep them equal unless an actual post-home move is
intended. The example uses a 10-second sequence timeout.
After installing/restarting with RAW_POS=1,HOMING=1 and the dedicated YAML:
PosOut01-Ena=0.Drv01-ModeAct returns to 9 and Enc01-PosScaled shows the expected
referenced drive position. Re-arm the output after checking the result.For example, substituting the actual PV prefixes:
caput <slave-prefix>PosOut01-Ena 0
caput <axis-motor-record>.HOMF 1
# After successful homing and verification:
caput <slave-prefix>PosOut01-Ena 1
The example’s motor record is named M1 under its configured IOC prefix. The output gate is not automatically coordinated with axis homing; these commands are separate. The hardware Home tab provides parameters and status; use the axis panel/motor record to start sequence 26.
On failure or timeout, stop/reset through the normal axis controls and verify the trigger is cleared and mode 9 is restored before resuming motion. Mode restoration after a successful home uses the post-home stage; do not assume an aborted sequence has completed that stage.
The DS402 axis writes its full controlword every cycle. Sequence 26 writes
its trigger earlier in the axis execution, so directly linking
trigg to driveControl01.4 would let the later whole-word write clear it.
With HOMING=1, the snippet instead adds:
Cfg.EcAddDataDT(ec<master>.s<slave>.driveControl01,0,4,1,B1,driveCmdExe01)
This follows the MCS2 approach. The B1 alias is initialized to zero and appended after the parent entry. During output-image transfer the parent controlword is written first; the alias then replaces only bit 4, preserving the other bits. Sequence 26 owns this alias and clears it when finished or stopped. The alias is not an additional PDO mapping.
The inspected ecmc RT loop executes in this order:
Axis-local PLC → motion axis → C++ logic → normal global PLCs → EtherCAT send
A normal global PLC can override an axis command after the axis executes;
an axis-local PLC cannot reliably override the parent’s whole-word writes.
However, with HOMING=1, the trigger alias is applied during output-image
transfer after those writes. A custom PLC/C++ homing implementation must
therefore write driveCmdExe01.0, not just driveControl01.4, and must not
compete with sequence 26 for that alias. Coordinate mode, velocity, axis
commands, timeout and output gates explicitly when replacing the built-in
sequence. Do not run both trigger owners together.
The execution order and writes were checked in ecmcMainThread.cpp,
ecmcDriveBase.cpp, ecmcAxisSequencer.cpp, ecmcEcSlave.cpp and
ecmcEcData.cpp. Verify the behavior in the deployed ecmc version when
using a custom override.
On the tested 100-full-step setup, a fresh start produced the first output edge after 100 full steps. After method-35 homing, the first edge was observed after 50 full steps, followed by transitions after another 100 steps: 50, 150, 250, … full steps of subsequent motion. This behavior was repeatable. The scaled position was reported to return to zero on homing.
The observation is a shift of the first-edge position; the following edge spacing remains 100 full steps. Here “edge” means an output state change, not a complete high/low pulse cycle. For the tested 200-step motor, 50 steps are 90 degrees and 100 steps are 180 degrees.
Homing once after startup, before beginning a measurement, is therefore a proposed way to obtain a consistent first edge after 50 full steps. The example does not automatically home at startup: command the normal M1 home sequence, verify completion and CSV restoration, then begin the measurement. Coordinate the output gate as described above. This proposal uses the reported repeatability; it does not establish behavior for other firmware, intervals, directions or restart conditions.
Sequence 26 detects a rising edge on the configured ready bit. Verify first and repeated method-35 requests: statusword bit 12 may already be high from a previous home, and a fast operation must still produce an observable completion transition. The sequence has no separate configured input for homing-error bit 13; monitor it in the Home tab and verify timeout/error behavior. Also check statusword bit 10, trigger clearing, mode restoration and first-edge behavior under other motion/restart conditions. The repeatable 100-step/50-step first-edge observation above does not establish all these cases. These are hardware commissioning checks, not outcomes established by the configuration tests.
| PV suffix | Meaning |
|---|---|
Enc01-PosAct | Fine 6063 counter with RAW_POS=1; otherwise legacy 6064 |
Enc01-PosScaled | Scaled 6064; present with RAW_POS=1 |
PosOut01-Ena through PosOut03-Ena | Individual output gates, each with -RB |
CfgRawPosition | Resolved raw-position option, read-only |
CfgHoming | Resolved homing option, read-only |
CfgCapture | Resolved capture option, read-only |
CfgAnalogIn | Resolved analog input option, read-only |
BO01-Arr | Complete output word, including the brake and output gates |
The hardware selects ecmcN6-1-1-1-S_OPT.ui and
ecmcN6-1-1-1-S_OPT_expert.ui. The usual position field shows fine feedback
with RAW_POS=1; the additional scaled field is visible with
CfgRawPosition=1. Counter readouts use integer precision.
Both displays have a Home tab. CfgHoming=1 reveals its homing fields;
otherwise it reports that the PDOs are not mapped. The compact tab shows
method, offset and actual mode readbacks. The expert tab adds editable
parameters/mode, command readbacks and statusword bits 10, 12 and 13.
The expert display also retains the output gate controls and readbacks.
The Home tab separates Mode and Speed fields; Speed shows the new drive
homing dynamics (editable in Expert, read-only in the compact display).
Capture and Analog tabs expose their optional readbacks only when
CfgCapture=1 / CfgAnalogIn=1. Capture has Home, In 3 and In 4 sub-tabs;
its control fields are readbacks, not writable arming controls.
The original panels remain available for the base descriptor.
After installing updated files, restart the IOC to load new records and reopen the panel to load its new layout. Changing the panel alone does not add missing IOC records.
The bench measurements support using raw 6063 as the fine open-loop
counter on FIR-v2542-B1080909 with 60E6:01=0. One approximate revolution
changed 6063 by 3,270,300 counts (about 359.29 degrees at the nominal scale)
and 6064 by two counts. The fine-counter axis and the 100-step output were
then reported working together.
The manual warns that 6063 values are invalid when the interface
resolution is zero. The observed open-loop behavior is therefore specific
evidence for this firmware/setup, not a guarantee for other firmware,
motor modes or sensors. Hardware-free checks cover mapping, component
validation, record links, gate masks and panel compilation/visibility;
they do not establish the drive’s waveform or homing behavior.
The initial 205C pulse-generator approach tried to retain native 6064
units. At 16,384 increments/full step, 100 full steps require a divider of
1,638,400, which does not fit the documented 16-bit ratio. A trial with one
pulse per full step still failed when selecting the pulse-generator source:
3203:01=8 repeatedly aborted with 0x06040047 (internal incompatibility).
Enabling nominal sensorless resolution with 60E6:01=3276800 subsequently
produced drive error 7305h (sensor 1 faulty). The working configuration
keeps 60E6:01=0, leaves feedback selection unchanged and writes neither
3203 nor 205C. The earlier pulse-generator example files are failed
prototypes, not the recommended configuration.
For the lab master 1, slave 0; adjust these addresses for another setup:
ethercat upload -m1 -p0 --type string 0x100A 0
ethercat upload -m1 -p0 --type uint16 0x6041 0
ethercat upload -m1 -p0 --type uint16 0x603F 0
ethercat upload -m1 -p0 --type uint32 0x60E6 1
ethercat upload -m1 -p0 --type uint32 0x60A8 0
ethercat upload -m1 -p0 --type uint16 0x3252 2
ethercat upload -m1 -p0 --type int32 0x6063 0
ethercat upload -m1 -p0 --type int32 0x6064 0
For the 100-step/output-1 setup, expect 60E6:01=0,
60A8=0x02AC0000 and 3252:02=0x0910. Sequential SDO uploads are not a
simultaneous position sample; stop motion when comparing paired readings.
6041 bit 3 identifies an active drive fault. 603F reports the last error
and may retain 7305 after its cause has gone. Reset a latched fault using
the normal drive controls once the cause is resolved. An SDO controlword
write while the axis owns the cyclic PDO will be overwritten.
For blank gate or homing fields, check record existence in the IOC shell:
dbgrep *PosOut*
dbgrep *CfgHoming*
dbgrep *HomeMethod*
There should be three gate controls and three gate readbacks. Homing
parameter records are present only with HOMING=1; capture and analog
records similarly require their options. Missing records require
updating the loaded configuration/database files and restarting the IOC.
6063, 607C, 6098, 323A and 3252.examples/PSI/lab_setup/N6/README_position_output_100_steps.md: lab setup and commissioning notes.docs/N6_position_output.md: component interface and constraints.Reusable SDO setup belongs in ecmccomp. Hardware PDOs, records and panels remain in ecmccfg, and examples choose components and parameter values.
| N6 lab file | Status |
|---|---|
cfg/position_output_100_steps.cmd | Compatibility wrapper for existing Drive-Generic-PositionOutput |
cfg/software_pwm_2khz.cmd | Compatibility wrapper for new Drive-Generic-PWMOutput |
cfg/pulse_per_fullstep.cmd | Failed pulse-generator reproducer; not a supported component |
cfg/disable_pulse_source.cmd | Lab-specific recovery for that failed trial; resets whole output word and feedback selections |
| Axis YAML files | Axis configuration: scaling, motion settings and sequence-26 homing |
Use masked gate PVs to disarm supported outputs normally. The failed trial and its broad recovery are deliberately not packaged as reusable components.